EasyManua.ls Logo

CHINT NVF5 Series - Page 143

CHINT NVF5 Series
148 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NVF5 Series User Manual Appendix B Parameter list
Code
Name
Setting Range
Default
Change
34 :
Rapid Current Limit
Overtime-E.CbC
35 :
Inverter Hardware
Overcurrent Abnormal-E.Inv
36:Load Loss-E.LL
37 :
PID
Feedback Loss in
Running Mode-E.FbL
38 :
Motor Over
Temperature-E.OT
39:Reserve
40:Reserve
41:
Excessive Speed
Deviation-E.dEv
42:Motor Over Speed-E.OS
43 ~ 55:Reserve
FE.30
Third Time(Latest)
Fault Frequency
(0.00 ~ 655.35)Hz
0.00Hz
●
FE.31
Third Time(Latest)
Fault Current
(0.00 ~ 655.35)A
0.00A
●
FE.32
Third Time(Latest)
Fault DC Bus Voltage
(0.00 ~ 655.35)V
0.00V
●
FE.33
Inverter Status of
The Third Time
(Latest)Fault
0 ~ 65535 0
●
FE.34
DI Terminal Status of
The Third Time
(Latest)Fault
0 ~ 9999 0
●
FE.35
DO Terminal Status of
The Third Time
(Latest)Fault
0 ~ 9999 0
●
FE.36 Fault Log2 0 ~ 55 0
●
FE.37 Fault Log 3 0 ~ 55 0
●
FE.38
Protection Selection1
in Fault Mode
0x0000 ~ 0x2222
Ones Place :
Motor Overload
E.OL1
0:Coast Stop
1:Stop per Stop Mode
2:Keep Running
Tens Place :
Input Phase
Loss-E.SPI (
Same as ones
place)
Hundreds Place: Output Phase
Loss-
E.SPO (
Same as ones
place)
0x0000
○
- 139 -