39
VOLTAGE/CURRENT CONSIDERATIONS
C4
Current (Amp) Voltage (VAC) Power (kW)
Max. Per Channel Range Nominal Working Per Channel Controller Total
164
(4x16A)
16
24 - 530 480
120 1.9 7.7
208 3.3 13.3
240 3.8 15.4
277 4.4 17.7
400 6.4 25.6
480 7.7 30.7
304
(4x30A)
30
120 3.6 14.4
208 6.2 25.0
240 7.2 28.8
277 8.3 33.2
400 12.0 48.0
480 14.4 57.6
404
(4x40A)
40
120 4.8 19.2
208 8.3 33.3
240 9.6 38.4
277 11.1 44.3
400 16.0 64.0
480 19.2 76.8
DISSIPATING CURVES