Configurable Alarms
Alarm is assigned to an output, configurable as: maximum, minimum, sym-
metrical, absolute/deviation, LBA, HB
Alarm Masking Exclusion at power-up, latch, reset by digital input
Diagnostics
SCR in short circuit (presence of current with control OFF)
SCR open (presence of voltage on SCR with control ON)
Load interrupted or no voltage (no current, no voltage on SCR with control ON)
Connection and Load Types
Selection with Dip-Switches
4 loads single-phase,
2 loads 3-phase, star without neutral controlled on two phases
2 loads 3-phase, closed triangle controlled on two phases
1 load 3-phase, star with neutral controlled on one phase
1 load 3-phase, open triangle controlled on one phase
(with 3-phase load, 4 CTs are needed if diagnostics is required)
GENERAL DATA
Power Supply 24VDC +/-25%, max 8VA
Indicators
Eight LEDS:
RN CPU in run state
ER Fault Signal
DI1, DI2 state of digital inputs
O1,...O4 state of outputs
Protection IP20
Work/Storage Temperature 0 - 50˚C (see dissipation curves) / -20˚C...70˚C
Relative Humidity 20 - 85% RH non-condensing
Ambient Work Conditions Indoor use, altitude up to 2000m
Installation DIN RAIL EN50022 or panel using screws
Installation Instructions
Installation category II, Pollution level 2, double isolation
Max surrounding air temperature 50˚C (for UL)
Open type equipment
Weight(s)
Models 30KW, 60KW, 80KW 1200g
Models 30KW, 60KW, with fuse holder 1600g