Advanced M52 Microprocessor User's Guide
ADVANCED M52UMCT2019 COLOR 11
Note: On/Off mode:
When operating in a Co-Work network all On/Off mode options are synchronized. Therefore,
turning off a unit, either by the touch screen when in Local, by the remote on/off at terminals 15
and 16 when in Remote, or through the schedule when in Timer mode will turn off all units in
that network.
To turn off an individual unit either as a stand-alone or in a Co-Work network see the Test Mode
section or simply open the disconnect switch.
Local/Remote RemoteON/OFF RemoteDem.Off StandbyStart UnitOperation
Local OFF OFF OFF STOP
Local ON OFF OFF RUN
Local OFF ON OFF Stop
Local OFF OFF ON RUN
Local ON ON OFF STOP
Local ON ON ON RUN
Local OFF ON ON RUN
Local OFF OFF OFF RUN
Local ON OFF OFF RUN
Local OFF ON OFF STOP
Local OFF OFF ON RUN
Local ON ON OFF STOP
Local ON ON ON RUN
Local OFF ON ON RUN
Remote OFF OFF OFF STOP
Remote ON OFF OFF RUN
Remote OFF ON OFF STOP
Remote OFF OFF ON RUN
Remote ON ON OFF STOP
Remote ON ON ON RUN
Remote OFF ON ON RUN
Remote OFF OFF OFF RUN
Remote ON OFF OFF RUN
Remote OFF ON OFF STOP
Remote OFF OFF ON RUN
Remote On ON OFF STOP
Remote On ON ON RUN
Remote OFF ON ON RUN