Advanced M52 Microprocessor User's Guide
ADVANCED M52UMCT2019 COLOR
50
Notes:
Operator can use the key pad at any display to log on. Once you logon to the network that
display can be selected to control any of the units. This is done by selecting the Co-work Icon in
the upper right hand corner of the display. A window will appear that shows all of the units in
the Co- work network. You can select from here the unit you would like to control as shown on
page 17.
When an alarm condition is detected the alarm is broadcast to all units in the network. The
alarm needs to be acknowledged at all units in the network.
When reviewing alarm in the Alarm tab or in the Historical Event log you must pay attention to
the PC board address to properly identify which unit in the network is alarming. This is the two
digit address that appears to the left of the event occurrence time in the Historical Event tab and
the Alarm tab. Events such as Unit on/off and Power Failure/Restore are shown for the
individual unit being poled.
You can program the network to display the temperature and humidity of the site (average of all
duty unit readings) or the individual temperature and humidity of the unit under the Settings tab.
Refer to the Setting section
Alarm Settings, Responses chart: