Advanced M52 Microprocessor User's Guide
ADVANCED M52UMCT2019 COLOR 7
Low-pressure switch remains closed after Pos. start time expires and compressor remains on.
Compressor stops when:
Loss of demand
Compressor contactor opens
Low pressure condition
Compressor stops when LP SW. opens. (Automatic reset) compressor contactor opens.
Short cycling alarm (Low Pressure)
After three consecutive low-pressure alarms in 60 mins, compressor contactor opens. Alarm must
be acknowledged and cleared before Compressor will start.
High pressure condition
Compressor stops when HP Switch opens. (Manual reset)
Compressor contactor opens. Compressor will not start until HP Switch is manually reset and
Alarm is acknowledged and cleared.
Thermal protection opens (automatic reset)
Line voltage cut-outs on all compressors except Specter compressor where the compressor module
causes a Compressor Overload alarm and stops the compressor through the microprocessor.
Compressor module resets after 30 minutes.
Note: Anytime the contactor opens the comp. elapse timer keeps compressor off for 3 minutes
(adjustable)
Chilled Water
On demand for cooling or dehumidification chilled water valve opens as demand signal ramps up
from 0 to 100%. Valve operates on 0-10 Vdc.
Valve closes when:
Loss of demand, signal diminishes to 0 Vdc
DX Demand (Dehumidification):
Cycles on compressors in stages 1 to 32 depending on Series and number of units connected together
with Co-Work as demand for dehumidification increases from 0 to 100%.
Variable speed fans (if available) will nominally slow down to accelerate this process. See settings
tab.
Demand for compressor:
Compressor contactor receives signal from microprocessor. Positive Start timer (Pos. start delay)
starts and bypasses LP switch for cold winter start-up. When HP switch is closed the start circuit
is complete and the compressor starts.
N/C auxiliary contact on compressor contactor opens and de-energizes receiver heaters. (Flooded
Condenser LAC)
N/C auxiliary contact on compressor contactor opens and de-energizes crankcase heater.
N/O auxiliary contact on compressor contactor enables fans on remote condenser. (Air-cooled
units only)
Low-pressure switch remains closed after Pos. start time expires and compressor remains on.
Rapid Dehumidification Feature (Series 6 units only)
If there is less than 20 percent demand for cooling and a demand for dehumidification the Dehum.
Solenoid valve (DSV) closes.