EasyManua.ls Logo

CLIVET ELFOControl2 - SYSTEM COMPONENT ADDRESSING; WSAN-XIN Unit Addressing

CLIVET ELFOControl2
80 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 49
SYSTEM COMPONENT ADDRESSING
WSAN-XIN
Parameters to be modified
Parameters Description Value
CF30 ModBus protocol controller Address 2
CF31
ModBus protocol Baud Rate (2=4800 / 3=9600
4 =19200)
3
CF32 Parity modbus 1=EVEN / 2=NONE / 3=ODD 2
CL43
DI4 Digital input Configuration
( remote OFF)
-2
CL44
DI5 Digital input Configuration
(remote Summer / Winter )
0
Press
+
PAr
Press
CL
Press
CF01
Select CF30
/
CF30
Press
0
Set the value
/
2
Confirm
2
Back to the previous menu
Select CF menu
/
CF
Repeat the sequence for the other parameters

Table of Contents