Area stata
For each areas you can read the data listed in the table below. There are 4 records for each area:
First area : area 1 => 150, area 2 => 154, area 3 => 158,…, area 12 => 194
Address Description Notes
150 Average temperature area 1
151 Average umidity area 1
152 Profile area 1 1 = off, 2 = area on eco mode, 3 = area on comfort mode
153 Setpoint area 1
Domestic hot water
Address Description Notes
200 DHW temperature
201 DHW second temperature
202 DHW profile
1 = Maintenance + recirculation, 2 = Maintenance,
3 = recirculation+ recharge, 4 = recharge
203 Solar temperature
204 Solar status 0 = disable, 1 = active
205 Heat pump DHW pump/ Recirculation 0 = disable, 1 = active
206 RHeater /DHW boiler 0 = disable, 1 = active
207 Antilegionella 0 = not in progress, 1 = in progress
ElfoFresh (EF) stata
For each ElfoFresh (EF) you can read the data listed in the table below. There are 9 records for each ElfoFresh:
First record : EF 1 => 210, EF 2 => 219, EF 3 => 228, EF 4 => 237
Address Description Notes
210 Supply temperature
211 Return temperature
212 Room humidity
213 Outdoor temperature
214 Room Setpoint
215 Status 0 = off, 1 = on
216 Compressor 0 = off, 1 = on
217 Dehumidify 0 = not in progress, 1 = In progress
218 Alarm 0 = not on alarm, 1 = alarm