EasyManuals Logo

CLIVET WiSAN-PME 1 S User Manual

CLIVET WiSAN-PME 1 S
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #12 background imageLoading...
Page #12 background image
12
About R-290 refrigerant
parts of the system
place the cylinder on the scale
start the recovery device and use it according to the
manufacturer's instructions
do not fill the cylinders excessively. (Do not exceed 80% of
the liquid volume)
do not exceed the maximum working pressure of the
cylinder, even temporarily
after filling the cylinders correctly and completing the
procedure, transfer the cylinders and equipment from
the site as soon as possible and close all shut-off valves
on the equipment.
before charging the recovered refrigerant into another
refrigeration system, it must be cleaned and checked.
3.3.17 Labelling
Remember that:
the device must be labelled to indicate that it has been
decommissioned and emptied of refrigerant
the label must be dated and signed
check that labels indicating the content of flammable
refrigerant are affixed to the device.
3.3.18 Recovery
When discharging refrigerant from a system for maintenan-
ce or decommissioning reasons.
Check that:
the refrigerant is removed safely
only cylinders suitable for refrigerant recovery are used
the number of cylinders required to hold the entire
system charge is available
all cylinders to be used are designed for the refrigerant
recovered and labelled for that refrigerant (special refri-
gerant recovery cylinders)
the cylinders are equipped with a pressure relief valve
and well-functioning shut-off valves
empty recovery cylinders are evacuated and, if possible,
cooled before recovery
the recovery equipment is in good working order, accom-
panied by a set of instructions at hand, and suitable for
the recovery of flammable refrigerants
a set of well-functioning calibrated scales is provided
the pipes are complete with decoupling fittings that are
leak-free and in good condition
the recovery equipment is in good working order, has
been properly maintained and the associated electrical
components are sealed to prevent a risk of ignition in
the event of refrigerant leakage. If in doubt, consult the
manufacturer.
the refrigerant is returned to the supplier in the correct
recovery cylinders, accompanied by the relevant waste
identification form
different types of refrigerant are not mixed in the reco-
very units, especially in the cylinders
if compressors or compressor oils are decommissioned,
evacuate them to an acceptable level to prevent flam-
mable refrigerant from remaining inside the lubricant
the evacuation procedure is carried out before returning
the compressor to the suppliers
only the electric heating on the compressor body is used
to accelerate this process
when oil is extracted from the system, it is drained using
a safe procedure.
3.3.19 Transportation, marking, storage and
disposal of units
comply with current national regulations.
3.3.20 Receipt and handling
On receipt of the unit:
check if there is refrigerant inside the packaging using an
electronic leak detector suitable for the system refrige-
rant
if there is, it is likely that the refrigerant circuit is dama-
ged
In this case, the unit must not be installed and the Techni-
cal Support Service must be called.
3.4 Safety area
Remember that:
the unit contains highly flammable refrigerant
there is a risk of fire and explosion
the refrigerant must be prevented from entering the
building
the refrigerant can form a combustible atmosphere by
mixing with the air
the refrigerant has a higher density than air, in the event
of a leak, spilled refrigerant can accumulate on the
ground and in vents
the safety area must not include neighbouring properties
or busy public areas
no structural changes may be made in the safety area
that would breach these regulations.
Preparation of the safety area
The unit must not be near:
windows, doors, shafts, basement entrances, hatches,
skylights
outside air inlets of ventilation systems
canals, downpipes, manholes, pumping wells, sewerage
ducting networks, etc.
The safety area must not contain ignition sources:
sockets, light wells, lamps or power switches
naked flames or flame bodies
electrical appliances that are not explosion-proof, mobile

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the CLIVET WiSAN-PME 1 S and is the answer not in the manual?

CLIVET WiSAN-PME 1 S Specifications

General IconGeneral
BrandCLIVET
ModelWiSAN-PME 1 S
CategoryHeat Pump
LanguageEnglish

Related product manuals