64
Technical data
15. Technical data
Heating
SIZE 2.1 3.1 4.1 5 .1 6.1 / 6.1T 7.1 / 7.1T 8.1 / 8.1T
Air 7°C - Water 35°C
Rated heating capacity 1 kW 4,50 6,20 8,40 10,0 12,0 14,0 15,0
Total power input 1 kW 0,87 1,27 1,68 2,13 2,50 3,11 3,41
COP 1 - 5,15 4,90 5,00 4,70 4,80 4,50 4,40
Water flow-rate 1 l/s 0,21 0,30 0,40 0,48 0,57 0,67 0,71
Nominal available pressure 1 kPa 85 85 86 86 88 88 88
Air 2°C - Water 35°C
Rated heating capacity 2 kW 4,40 5,60 7,10 8,20 9,10 10,1 12,8
Total power input 2 kW 1,07 1,44 1,84 2,25 2,39 2,81 4,00
COP 2 - 4,10 3,90 3,85 3,65 3,80 3,60 3,20
Water flow-rate 2 l/s 0,21 0,27 0,34 0,39 0,43 0,48 0,61
Nominal available pressure 2 kPa 85 85 86 86 88 88 88
Air -7°C - Water 35°C
Rated heating capacity 3 kW 4,50 5,90 7,00 8,00 10,0 11,5 12,7
Total power input 3 kW 1,45 2,00 2,33 2,81 3,57 4,00 4,26
COP 3 - 3,10 2,95 3,00 2,85 2,80 2,70 2,50
Water flow-rate 3 l/s 0,21 0,28 0,33 0,38 0,48 0,52 0,55
Nominal available pressure 3 kPa 85 85 86 86 88 88 88
Air 7°C - Water 45°C
Rated heating capacity 4 kW 4,50 6,40 8,20 10,0 12,0 14,0 15,0
Total power input 4 kW 1,11 1,68 2,13 2,74 3,24 4,00 4,48
COP 4 - 4,05 3,80 3,85 3,65 3,70 3,50 3,35
Water flow-rate 4 l/s 0,21 0,30 0,39 0,48 0,57 0,67 0,71
Nominal available pressure 4 kPa 85 85 86 86 88 88 88
Air 7°C - Water 55°C
Rated heating capacity 5 kW 4,60 6,20 7,80 9,50 12,0 14,0 15,0
Total power input 5 kW 1,44 2,00 2,44 3,11 3,87 4,67 5,26
COP 5 - 3,20 3,10 3,20 3,05 3,10 3,00 2,85
Water flow-rate 5 l/s 0,14 0,18 0,23 0,28 0,36 0,42 0,45
Nominal available pressure 5 kPa 85 85 86 86 88 88 88
Data according to EN 14511:2018.
1. inlet/outlet water temperature 30/35°C, outdoor air temperature 7°C dry bulb / 6°C wet bulb
2. inlet/outlet water temperature 30/35°C, outdoor air temperature 2°C dry bulb / 1°C wet bulb
3. inlet/outlet water temperature 30/35°C, outdoor air temperature 7°C dry bulb / 8°C wet bulb
4. water inlet/outlet temperature 40/45°C, outdoor air temperature 7°C dry bulb / 6°C wet bulb
5. water inlet/outlet temperature 47/55°C, outdoor air temperature 7°C dry bulb / 6°C wet bulb
Data according to EN 14511:2018.
1. inlet/outlet water temperature 30/35°C, outdoor air temperature 7°C dry bulb / 6°C wet bulb
SIZE 2.1 3.1 4.1 5 .1 6.1 / 6.1T 7.1 / 7.1T 8.1 / 8.1T
Air 7°C - Water 35°C
Silent mode 1
Rated heating capacity 1 kW 3,34 4,64 6,37 7,50 9,06 10,53 11,17
Total power input 1
kW 0,64 0,91
1,18 1,46 1,77 2,12
2,28
COP 1 - 5,25 5,12 5,39 5,12 5,11 4,97 4,89
Water flow-rate 1 l/s 0,16 0,22 0,30 0,36 0,43 0,50 0,53
Nominal available pressure 1 kPa 85 85 86 86 88 88 88
Silent mode 2
Rated heating capacity 1 kW 2,93 3,15 4,40 4,97 5,87 7,07 7,50
Total power input 1 kW 0,55 0,60 0,78 0,90 1,05 1,31 1,41
COP 1 - 5,32 5,26 5,64 5,52 5,61 5,38 5,31
Water flow-rate 1 l/s 0,14 0,15 0,21 0,24 0,28 0,34 0,36
Nominal available pressure 1 kPa 85 85 86 86 88 88 88