Technical data
SIZE 2.1 3.1 4.1 5 .1 6.1T / 6.1 7.1T / 7.1 8.1T / 8.1
C° 18 C - Water° 35 Air
Nominal cooling capacity 1 kW 4,50 6,50 8,30 10,0 12,0 14,0 16,0
Total power input 1 kW 0,82 1,27 1,61 2,11 2,67 3,33 4,10
EER 1 - 5,50 5,10 5,15 4,75 4,50 4,20 3,90
Water flow-rate 1 l/s 0,21 0,31 0,40 0,48 0,57 0,67 0,76
Nominal available pressure 1 kPa 85 85 86 86 88 88 88
C° 7 C - Water° 35 Air
Nominal cooling capacity 2 kW 4,70 6,80 7,50 8,90 11,5 12,7 14,0
Total power input 2 kW 1,29 2,19 2,17 2,74 3,77 4,38 5,09
EER 2 - 3,65 3,10 3,45 3,25 3,05 2,90 2,75
Water flow-rate 2 l/s 0,22 0,32 0,36 0,42 0,55 0,60 0,67
Nominal available pressure 2 kPa 85 85 86 86 88 88 88
Cooling
Data according to EN 14511:2018.
1. water inlet/outlet temperature 23/18°C, outdoor air temperature 35°C dry bulb / 27°C wet bulb
2. water inlet/outlet temperature 12/7°C, outdoor air temperature 35°C dry bulb / 27°C wet bulb
Data according to EN 14511:2018.
1. water inlet/outlet temperature 23/18°C, outdoor air temperature 35°C dry bulb / 27°C wet bulb
SIZE 2.1 3.1 4.1 5 .1 6.1 / 6.1T 7.1 / 7.1T 8.1 / 8.1T
Air 35°C - Water 18°C
Silent mode 1
Nominal cooling capacity 1 kW 3.42 4.91 6.19 7.48 9.06 10.51 12.15
Total power input 1 kW 0.57 0.90 1.02 1.36 1.64 1.99 2.48
EER 1 - 5.98 5.48 6.08 5.51 5.54 5.29 4.90
Water flow-rate 1 l/s 0.16 0.23 0.29 0.36 0.43 0.50 0.58
Nominal available pressure 1 kPa 85 85 86 86 88 88 88
Silent mode 2
Nominal cooling capacity 1 kW 3.25 3.29 4.69 5.04 6.08 6.99 7.99
Total power input 1 kW 0.54 0.55 0.75 0.81 1.06 1.25 1.45
EER 1 - 6.01 6.00 6.27 6.23 5.72 5.61 5.50
Water flow-rate 1 l/s 0.15 0.16 0.22 0.24 0.29 0.33 0.38
Nominal available pressure 1 kPa 85 85 86 86 88 88 88