66
Technical data
SIZES 2.1 3.1 4.1 5.1 6.1 7.1 8.1 6.1T 7.1T 8.1T
Average climatic conditions - Heat pump for Average temperature application
Nominal power 1 kW 4,90 5,90 6,80 7,80 12,0 13,0 14,4 12,0 13,0 14,4
SCOP
1 - 3,79 3,82 3,82 3,82 3,62 3,62 3,57 3,620 3,623 3,573
Generator energy class 1 - ++A ++A ++A ++A ++A ++A ++A ++A ++A ++A
ηs 1 % 148,7 149,7 149,7 149,8 141,8 141,9 139,9 141,8 141,9 139,9
Average climatic conditions - Heat pump for Low temperature application
Nominal power 2 kW 5,00 6,40 8,00 9,20 12,1 13,7 14,7 12,1 13,7 14,7
SCOP
2 - 5,09 4,91 5,20 5,07 4,68 4,64 4,59 4,675 4,635 4,590
Generator energy class 2 - +++A +++A +++A +++A +++A +++A +++A +++A +++A +++A
ηs
2 % 200,7 193,5 204,8 199,8 184,0 182,4 180,6 184 182,4 180,6
Average climatic conditions - Heat pump for application with Fan coil
Nominal power 3 kW 4,70 6,80 7,50 8,90 11,5 12,7 14,0 11,5 12,7 14,0
SEER
3 - 5,23 5,32 5,86 5,55 5,19 5,18 5,12 5,185 5,178 5,115
ηs
3 % 206,3 209,8 231,3 218,8 204,4 204,1 201,6 204,4 204,1 201,6
The product is conforming with the European ErP Directives, which includes Commission Delegated Regulation (EU) no. 811/2018 and Commission Delegated Regulation no. 813/2018.
Data according to EN 14825
1. Average climate, Medium temperature 47/55°C
2. Average climate, Low temperature 30/35°C
3. Average climate, Low temperature 12/7°C
ErP
1. It contains fluorinated greenhouse gases
2. Consider the water content of the area with less volume
3. Sucient volume up to a maximum of 60 litres of water content in the system.
4. Sound power levels are determined using the intensimetric method (UNI EN ISO 9614-2). Data referring to the following conditions at full load.
Heating: water inlet/outlet temperature 47/55°C, outdoor air temperature 7°C.
Cooling: water inlet/outlet temperature 12/7°C, outdoor air temperature 35°C.
Technical characteristics
SIZE 2.1 3.1 4 .1 5.1 6 .1 7.1 8.1 6.1T 7.1T 8.1T
Refrigeration circuit
Compressor
n°/tipo - - 1 1 1 1 1 1 1 1 1 1
tipo - - Twin Rotary
Oil carica - ml 600 830 1100
Refrigerant
tipo/GWP 1 - R290 / 3
carica - kg 0,70 0,70 1,10 1,10 1,25 1,25 1,25 1,25 1,25 1,25
CO
2
equiv. - kg CO
2
2 2 3 3 4 4 4 4 4 4
Fans
numero
-
- 1 1 1 1 1 1 1 1 1 1
portata - m
3
/h 2875 4031 4457 5042 4457 5042
Water circuit
Minimum system water content - l 30 70
Admissible water flow rate
minima 2 l/s 0,10 0,17
massima - l/s 0,42 0,42 0,64 0,69 0,89 1,00 1,08 0,89 1,00 1,08
Maximum system pressure - bar 3 3 3 3 3 3 3 3 3 3
System expansion vessel
volume 3 l 8
precarica - bar 8
Hydraulic connections - inch G1"BSP G5/4"BSP
Sound data
Sound pressure at 1 metre 4 dB(A) 44 46 48 49 51 52 56 51 52 56
Sound power 4 dB(A) 56 58 60 61 65 65 69 65 65 69
Dimensions and weights
Dimensions
(Length x Height x Depth)
unità - mm 1295*718*381 1385*865*423
imballo - mm 1375*885*475 1465*1035*560
Weight
unità - kg 90 117 135 137
imballo - kg 110 157 159