25
7 - START-UP
CLIMATICA TExt
Only if P0053: En Climatica ≠ 0
The setpoint defined by the temperature curve is shown at
status S0010: ActualSptTExt
P0265:CSptLow Set Point → AirAtSptLowC
P0266:AirAtSptLowC TEXT → SptLowC
P0267:CSptHigh Set Point → AirAtSptHigC
P0268:AirAtSptHigC TEXT → SptHigC
Eg 1:
Eg 2:
Water Reset
pwd
Only if P0051: En WaterReset ≠ 0
The water reset correction affects the setpoint defined by the
Climate curve TExt (actual setpoint).
The setpoint is shown at status S0011: ActualSptWR
P0281:MaxCWRC
Maximum correction to be applied to the
setpoint
P0283:SWRMaxC
Value of the WR control signal
corresponding to the correction of the
set COOL equal to the parameter P281
P0285:SWRMinC
Value of the WR control signal
corresponding to the correction of the
set COOL equal to 0
DemandLimit
pwd
It is possible to limit the absorbed electric power with an
external signal 0-10 Vcc.
The higher the signal is, the lower the number of compressors
available to meet the thermal need .
Only if P0050:En DemandLimit ≠ 0
P0009:set demand limit
Parameter setting of the value
% of demand limit