34
7 - CONTROL
ALARMS - TAB 2
code description description t.i. module input t.a.
EE025 Pump 3 overload Pump 3 thermal protection DI 965 hydronic T1 X6 A
EE026 Inverter overload Inverter overload DI 965 hydronic T5 DL1 A
ee027 water IN temp Water inlet temperature probe faulty AI 687 central T1 B1 A
ee028 Water OUT temp Water outlet temperature probe faulty AI 687 central T1 B2 A
ee029 External air temp External air temperature probe faulty AI 687 central T1 B3 A
ee030 Demand Limit Signal logoff or short circuit AI 687 central T2 X1 A
ee031 WaterReset Signal logoff or short circuit AI 687 central T2 X2 A
ee032: External Humidity probe External Humidity probe faulty AI 687 central T2 X3 A
ee033: Cabinet temperature Cabinet temperature probe faulty AI 687 central T2 X4 A
ee034: Timout hydronic module Logoff Hydronic module periperal bus A
ee101: Timoeout circuit module Logoff circuit 1 module periperal bus A
ee102: Timeout comm. Driver Logoff driver 1 module periperal bus A
ee103:
Timeout comm. Module
rec
Logoff recovery module periperal bus A
ee104: EEV blocked Driver 1 blocked 94U driver A
EE106: Comp 1 protections Compressor 1 thermal protection DI 985 circuit 1 T4 D1 M
EE107: Comp 2 protections Compressor 2 thermal protection DI 985 circuit 1 T4 D2 M
EE108: Comp 3 protections Compressor 3 thermal protection DI 985 circuit 1 T4 D3 M
EE118: source side protection Source side protection DI 985 circuit 1 T9 DL2 M
ee122: discharge temp. C1 Faulty probe - discharge temperature compressor 1 AI 985 circuit 1 T1 B1 A
ee123: discharge temp. C2 Faulty probe - discharge temperature compressor 2 AI 985 circuit 1 T1 B2 A
ee124: discharge temp. C3 Faulty probe - discharge temperature compressor 3 AI 985 circuit 1 T2 X2 A
ee125: source1 temp. Faulty probe - source 1 temperature AI 985 circuit 1 T1 B3 A
ee126: source2 temp. Faulty probe - source 2 temperature AI 985 circuit 1 T2 X1 A
ee127: Suction temperature Faulty probe - Suction temperature AI 94U driver T2 X2 A
ee128: discharge pressure Faulty probe - discharge pressure AI 985 circuit 1 T2 X3 A
ee129: suction pressure Faulty probe - suction pressure AI 94U driver T1 X1 A
ee130: Rec. Gas temperature Faulty probe - Recovery gas temperature AI 965 recovery T1 X1 A
ee131: Rec. Pressure Faulty probe - Recovery gas pressure AI 965 recovery T2 X7 A
ee132: Water In rec. Temp. Faulty probe - Water recovery inlet AI 965 recovery T1 X2 A
ee133: Water out rec. Temp. Faulty probe - Water recovery outlet AI 965 recovery T1 X3 A
ee135: Bsp 985 wrong Bios wrong version 985 circuit 1 A
ff105: min overheating Low overheating C1 A
fF109: Low pressure from DI Low pressure from digital input DI 985 circuit 1 T3 X7 A/M