7 - CONTROL
STATI MASTER SLAVE
code description description
S0600 SetPoint Unit1
Value accessible from the display of the unit machine network master.
Working setpoint master unit (Address 1 on periferalbus)
S0601 SetPoint Unit2
Value accessible from the display of the unit machine network master.
Working setpoint unit 2 (Address 2 on periferalbus)
S0602 SetPoint Unit3
Value accessible from the display of the unit machine network master.
Working setpoint unit 3 (Address 3 on periferalbus)
S0603 SetPoint Unit4
Value accessible from the display of the unit machine network master.
Working setpoint unit 4 (Address 4 on periferalbus)
S0604 SetPoint Unit5
Value accessible from the display of the unit machine network master.
Working setpoint unit 5 (Address 5 on periferalbus)
S0605 SetPoint Unit6
Value accessible from the display of the unit machine network master.
Working setpoint unit 6 (Address 6 on periferalbus)
S0606: SetPoint Unit7
Value accessible from the display of the unit machine network master.
Working setpoint unit 7 (Address 7 on periferalbus)
S0607: StatusUnit1
Value accessible from the display of the unit machine network master.
Status master unit 7 0=Off 1=Eco 2=On 3=PmpOn
S0608: StatusUnit2
Value accessible from the display of the unit machine network master.
Status unit 2 0=Off 1=Eco 2=On 3=PmpOn
S0609: StatusUnit3
Value accessible from the display of the unit machine network master.
Status unit 3 0=Off 1=Eco 2=On 3=PmpOn
S0610: StatusUnit4
Value accessible from the display of the unit machine network master.
Status unit 4 0=Off 1=Eco 2=On 3=PmpOn
S0611: StatusUnit5
Value accessible from the display of the unit machine network master.
Status unit 5 0=Off 1=Eco 2=On 3=PmpOn
S0612: StatusUnit6
Value accessible from the display of the unit machine network master.
Status unit 6 0=Off 1=Eco 2=On 3=PmpOn
S0613: StatusUnit7
Value accessible from the display of the unit machine network master.
Status unit 7 0=Off 1=Eco 2=On 3=PmpOn

Table of Contents

Other manuals for CLIVET WSAT-XEE Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the CLIVET WSAT-XEE Series and is the answer not in the manual?

CLIVET WSAT-XEE Series Specifications

General IconGeneral
BrandCLIVET
ModelWSAT-XEE Series
CategoryChiller
LanguageEnglish

Related product manuals