8.6.1 Error handling configuration of a Nonstop-installation
Error / Warning Master Slave
1 Not Ready Ignore error # 1 Ignore error # 1
2 TUNIT / Paperend Stop at error # 2 Stop at error # 2
3 Position too short Ignore error # 3 Ignore error # 3
4 Max. Speed Ignore error # 4 Ignore error # 4
5 Label Stock Continue at error # 5 Continue at error # 5
6 Rewinder full Continue at error # 6 Continue at error # 6
7 No LSC-adjust Ignore error # 7 Ignore error # 7
8 Nonstopmode Stop at error # 8 Stop at error # 8
9 Label too long Stop at error # 9 Stop at error # 9
10 LSC Counter Ignore error # 10 Ignore error # 10
11 Drive not Ready Stop at error # 11 Stop at error # 11
12 Undervoltage Ignore error # 12 Ignore error # 12
13 Profiling speed Ignore error # 13 Ignore error # 13
14 Wstchdog Timer Ignore error # 14 Ignore error # 14
15 Division by zero Ignore error # 15 Ignore error # 15
16 Predisp. too short Ignore error # 16 Ignore error # 16
Remarks to the error #:
1 if READY-signal is used, set Master/Slave to "Stop at..."
3 set to "Continue at..." for setup/programming, set to "Ignore..." in production
4 If conveyor speed is not checked externally, set Master/Slave to "Stop at...."
7 set to "Continue at..." for setup/programming, set to "Ignore..." in production
8 This error is not used anymore (Version 1.20 and later)
10 set to "Continue at..." for setup/programming, set to "Ignore..." in production
16 set to "Continue at..." for setup/programming, set to "Ignore..." in production
5999.530-01E 14.01.2004 CSWM 4 50