ID-FLX Lite Global Guide
131
Setpoint group Load limit Related FW 2.5.0
Range [units] -10000 .. +10000 [-]
Default value 0 YES
Step 1
Comm object 11845 Related applications
Description
Regulator requested value when LBI Request2 is active.
Value of this Setpoint should be given in value of quantity without decimal point.
Example: When AIN is configured in such way that Load limit set on 5V to maintain the value
8.54bar, then the value inserted to this Setpoint is 854.
Request 2
6 back to List of setpoints
Setpoint group Load limit Related FW 2.5.0
Range [units] -2000.0 .. +2000.0 [%]
Default value 10 YES
Step 0.1
Comm object 11846 Related applications
Description
This setpoint is giving regulator gain factor. See Note below.
Reg Gain
6 back to List of setpoints
Setpoint group Load limit Related FW 2.5.0
Range [units] 0.0 .. 1000.0 [%]
Default value YES
Step 0.1
Reg Integral