ID-FLX Lite Global Guide
207
Related FW 2.5.0 Related applications
Comm object 3
Description
Output closes when any warning alarm appears.
The output opens, if
No warning alarm is active and
FAULT RESET is pressed
Common Wrn
6 back to List of LBO
Related FW 2.5.0 Related applications
Comm object 4
Description
Output closes when any shutdown alarm appears.
The output opens, if
No Sd alarm is active and
FAULT RESET is pressed
Common Sd
6 back to List of LBO
Related FW 2.5.0 Related applications
Comm object 257
Description
Output closes when any cooldown alarm appears.
The output opens, if
No Cd alarm is active and
FAULT RESET is pressed
Common Cd
6 back to List of LBO
Related FW 2.5.0 Related applications
Comm object 6
Description
Output closes when any sensor fail alarm appears.
The output opens, if
No warning alarm is active and
FAULT RESET is pressed
Common Fls
6 back to List of LBO