InteliLite Global Guide
161
Subgroup: Controller settings
Setpoint group Basic settings Related FW 1.2.1
Range [units] OFF / MAN / AUTO / TEST [-]
Default value OFF Alternative config NO
Step [-]
Comm object 8315 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
This setpoint can be used for changing the Controller mode remotely, e.g. via MODBUS. Use the mode
selector on the main screen for changing the mode from the front panel. Use mode selector in the control
window for changing the mode from LiteEdit2015.
Controller mode
6 back to List of setpoints
Setpoint group Basic settings Related FW 1.2.1
Range [units] 1 .. 32 [-]
Default value 1 Alternative config NO
Step 1
Comm object 24537 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Controller identification number. It is possible to set controller address different from the default value (1) so
that more IL controllers can be interconnected (via RS485) and accessed e.g. from MODBUS terminal.
Note: When opening connection to the controller it's address has to correspond with the setting in PC
tool.
Note: This setpoint is common for CM-Ethernet, CM-GPRS and CM-4G-GPS modules.
Controller Address
6 back to List of setpoints

Table of Contents

Other manuals for ComAp InteliLite MRS16

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite MRS16 and is the answer not in the manual?

ComAp InteliLite MRS16 Specifications

General IconGeneral
BrandComAp
ModelInteliLite MRS16
CategoryController
LanguageEnglish

Related product manuals