InteliLite Global Guide
160
Setpoint group Basic settings Related FW 1.2.1
Range [units] FGen->RPM / 1 .. 500 [-]
Default value 120 Alternative config NO
Step 1
Comm object 8252 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
Number of teeth on the engine flywheel where the pick-up is installed. Set to zero if no pick-up is used and
the Engine speed will be counted from the generator frequency.
Note: If no pickup is used, the D+ or W terminal should be used to prevent possible overcranking, which
can occur if at least 25% of nominal generator voltage is not present immediately after exceeding firing
speed.
Gear Teeth
6 back to List of setpoints
Setpoint group Basic settings Related FW 1.2.1
Range [units] 100 .. 4 000 [RPM]
Default value 1 500 RPM Alternative config YES
Step 1 RPM
Comm object 8253 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
Nominal engine speed (RPM - revolutions per minute).
Note: To lock this setpoint against editing you also have to lock setpoint Nominal RPM 1 (page 291) and
Nominal RPM 2 (page 294).
Nominal RPM
6 back to List of setpoints