InteliLite Global Guide
291
Setpoint group Basic settings Related FW 1.2.1
Range [units] 1 .. 10 000 [A]
Default value 350 A Alternative config YES
Step 1 A
Comm object 12049 Related applications AMF, MRS
Config level Standard
Setpoint visibility
Conditioned by the setpoint Connection Type 1 (page 290).
Description
When logical binary input CONFIGURATION 2 (PAGE 450) isn’t active, then setpoint Nominal Current (page
156) has the same value as setpoint Nominal Current 1. Setpoint Nominal Current (page 156) can be
changed from both places - from Basic settings setpoint group and from Alternate Config setpoint group.
Nominal Current 1
6 back to List of setpoints
Setpoint group Basic settings Related FW 1.2.1
Range [units] 45 .. 65 [Hz]
Default value 50 Hz Alternative config YES
Step 1 Hz
Comm object 9913 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
When logical binary input CONFIGURATION 2 (PAGE 450) isn’t active, then setpoint Nominal Frequency (page
159) has the same value as setpoint Nominal Frequency 1. Setpoint Nominal Frequency (page 159) can be
changed from both places - from Basic settings setpoint group and from Alternate Config setpoint group.
Nominal Frequency 1
6 back to List of setpoints
Setpoint group Basic settings Related FW 1.2.1
Range [units] 100 .. 4 000 [RPM]
Default value 1 500 RPM Alternative config YES
Step 1 RPM
Comm object 9915 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
When logical binary input CONFIGURATION 2 (PAGE 450) isn’t active, then setpoint Nominal RPM (page 160)
has the same value as setpoint Nominal RPM 1. Setpoint Nominal RPM (page 160) can be changed from
both places - from Basic settings setpoint group and from Alternate Config setpoint group.
Nominal RPM 1
6 back to List of setpoints

Table of Contents

Other manuals for ComAp InteliLite MRS16

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite MRS16 and is the answer not in the manual?

ComAp InteliLite MRS16 Specifications

General IconGeneral
BrandComAp
ModelInteliLite MRS16
CategoryController
LanguageEnglish

Related product manuals