InteliLite Global Guide
156
Setpoint group Basic settings Related FW 1.2.1
Range [units] 1 .. 5 000 [kW]
Default value 200 kW Alternative config Yes
Step 1 kW
Comm object 8276 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Nominal power of the gen-set. Generator Overload BOC (page 194) protection is based on this setpoint.
Note: This setpoint is used when setpoint Connection type (page 157) is adjusted to Monophase or
Splitphase or 3Ph3Wire or High Leg D or 3Ph4Wire or when Autodetect detects connection type as
3Ph3Wire or High Leg D or 3Ph4Wire.
Nominal Power
6 back to List of setpoints
Subgroup: Current settings
Setpoint group Basic settings Related FW 1.2.1
Range [units] 1 .. 10 000 [A]
Default value 350 A Alternative config YES
Step 1 A
Comm object 8275 Related applications AMF, MRS
Config level Standard
Setpoint visibility
Conditioned by the setpoint Connection type (page 157).
Description
It is current limit for generator IDMT Overcurrent Delay (page 196) and Short Circuit BOC (page 195)
protections and means maximal continuous generator current. Nominal Current can be different from
generator rated current value.
Note: To lock this setpoint against editing you also have to lock setpoint Nominal Current 1 (page 291)
and Nominal Current 2 (page 293).
Nominal Current
6 back to List of setpoints

Table of Contents

Other manuals for ComAp InteliLite MRS16

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite MRS16 and is the answer not in the manual?

ComAp InteliLite MRS16 Specifications

General IconGeneral
BrandComAp
ModelInteliLite MRS16
CategoryController
LanguageEnglish

Related product manuals