InteliLite Global Guide
157
Setpoint group Basic settings Related FW 1.2.1
Range [units] 1 .. 5 000 [A/5A]
Default value 2 000 A/5A Alternative config NO
Step 1 A/5A
Comm object 8274 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Gen-set current transformers ratio.
Note: Generator currents and power measurement is suppressed if current level is below 1% of CT
range.
CT Ratio
6 back to List of setpoints
Subgroup: Voltage settings
Setpoint group Basic settings Related FW 1.2.1
Range [units] Mono Phase / SplitPhase / 3Ph3Wire / High Leg D / 3Ph4Wire / Autodetect [-]
Default value 3Ph4Wire Alternative config YES
Step [-]
Comm object 11628 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Mono Phase Single phase voltage measurement L1-N
1x CT (Current Transformer)
Split Phase Double Delta connection
Split Phase
Two phase voltage measurement L1,L2 with 180° phase shift
2x CT (Current Transformer)
3Ph3Wire Ungrounded Delta connection
Open Delta
Ungrounded Wye
Corner-Grounded Delta
Split Phase Delta
Three phase voltage measurement L1,L2,L3 with 120° phase shift
No neutral is available 3x CT (Current Transformer)
High Leg D High Leg Delta connection
Generator winding connection system
Connection type