EasyManua.ls Logo

ComAp InteliLite MRS16 - Page 195

ComAp InteliLite MRS16
632 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
InteliLite Global Guide
195
Subgroup: Current Protection
Setpoint group Generator settings Related FW 1.2.1
Range [units] 100 .. 500 [%]
Default value 250 % Alternative config NO
Step
1 % of Nominal Current (page 156)
Comm object 8282 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
BOC occurs when generator current reaches this preset threshold.
Note: When there is no control of breakers, the type of protection is Sd not BOC.
Short Circuit BOC
6 back to List of setpoints
Setpoint group Generator settings Related FW 1.2.1
Range [units] 0,00 .. 10,00 [s]
Default value 0,04 s Alternative config YES
Step 0,01 s
Comm object 9991 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
Delay for Short Circuit BOC (page 195) protection.
Short Circuit BOC Delay
6 back to List of setpoints

Table of Contents

Other manuals for ComAp InteliLite MRS16

Related product manuals