InteliLite Global Guide
292
Setpoint group Basic settings Related FW 1.2.1
Range [units] 80 .. 20 000 [V]
Default value 231 V Alternative config YES
Step 1 V
Comm object 12052 Related applications AMF, MRS
Config level Standard
Setpoint visibility
Conditioned by the setpoint Connection Type 1 (page 290).
Description
When logical binary input CONFIGURATION 2 (PAGE 450) isn’t active, then setpoint Nominal Voltage Ph-N
(page 158) has the same value as setpoint Nominal Voltage Ph-N 1 . Setpoint Nominal Voltage Ph-N (page
158) can be changed from both places - from Basic settings setpoint group and from Alternate Config
setpoint group.
Nominal Voltage Ph-N 1
6 back to List of setpoints
Setpoint group Basic settings Related FW 1.2.1
Range [units] 80 .. 40 000 [V]
Default value 400 V Alternative config YES
Step 1 V
Comm object 12055 Related applications AMF, MRS
Config level Standard
Setpoint visibility
Conditioned by the setpoint Connection Type 1 (page 290).
Description
When logical binary input CONFIGURATION 2 (PAGE 450) isn’t active, then setpoint Nominal Voltage Ph-Ph
(page 159) has the same value as setpoint Nominal Voltage Ph-Ph 1. Setpoint Nominal Voltage Ph-Ph (page
159) can be changed from both places - from Basic settings setpoint group and from Alternate Config
setpoint group.
Nominal Voltage Ph-Ph 1
6 back to List of setpoints