InteliLite Global Guide
163
Setpoint group Basic settings Related FW 1.2.1
Range [units] Disabled / 1 .. 599 [s]
Default value 10 s Alternative config NO
Step 1 s
Comm object 8264 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
Setting of horn behavior.
Disabled Disabling the Horn sounding function
1 .. 599 [s]
Timeout for HORN (PAGE 502) binary output. The HORN (PAGE 502) output is opened when
this timeout elapsed.
Note: Horn timeout starts again from the beginning if a new alarm appears before previous Horn timeout
has elapsed.
Horn Timeout
6 back to List of setpoints
Setpoint group Basic settings Related FW 1.2.1
Range [units] Disabled / 1 - 360 [min]
Default value Disabled Alternative config NO
Step 1 min
Comm object 8548 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
The controller is switched to Zero Power Mode when there is no user interaction with the controller for the
preset time period. Zero Power Mode is disabled in AMF automatic mode. For the controller wake up press
button Start or activate Binary Input 1. The controller will not switch to Zero Power Mode if generator is
running. In Zero Power Mode binary outputs go to high impedance.
Zero Power Mode
6 back to List of setpoints

Table of Contents

Other manuals for ComAp InteliLite MRS16

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite MRS16 and is the answer not in the manual?

ComAp InteliLite MRS16 Specifications

General IconGeneral
BrandComAp
ModelInteliLite MRS16
CategoryController
LanguageEnglish

Related product manuals