InteliLite Global Guide
164
Setpoint group Basic settings Related FW 1.2.1
Range [units] PwrFactor / ATT [-]
Default value PwrFactor Alternative config NO
Step [-]
Comm object 13346 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
Setpoint adjust value which is shown on main screen.
PwrFactor: Value of power factor is shown on main screen.
ATT:
This option is for Tier IV Final support. In this case value of DEF Level is shown on main
screen.
Main Screen
6 back to List of setpoints
Group: Engine settings
Subgroup: Starting
Setpoint group Engine settings Related FW 1.2.1
Range [units] Diesel / Gas [-]
Default value Diesel Alternative config NO
Step [-]
Comm object 9100 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
Determines behavior of the Binary output FUEL SOLENOID (PAGE 493)
Diesel: Output closes before binary output STARTER (PAGE 510). Lead of output is adjusted via setpoint
Fuel Solenoid Lead (page 169). The output opens if Emergency Stop comes or gen-set is stopped
and in pause between repeated starts.
Gas: Output closes together with binary output IGNITION (PAGE 503) if RPM is over the 30 RPM (fixed
value). Output opens after stop command or in pause between repeated start.
Fuel Solenoid
6 back to List of setpoints