InteliLite Global Guide
493
LBO: F
Related FW 1.2.1 Related applications AMF, MRS
Comm object 592
Description
When the Fault Reset button is pressed the output is active for 1 s.
Fault Reset
6 back to Logical binary outputs alphabetically
Related FW 1.2.1 Related applications AMF, MRS
Comm object 1253
Description
Output closes when the value of Fuel Level lies under the value of Fuel Pump On (page 186) setpoint and
opens when value of Fuel Pump Off (page 187) is reached.
This output also can be closed by binary input FUEL PUMP ON/OFF (PAGE 454). In this case the binary
output FUEL PUMP ON (PAGE 186) is closed until the binary input FUEL PUMP ON/OFF (PAGE 454) is active
or until the value of Fuel Pump Off (page 187) is reached.
Note: Setpoints Fuel Pump On (page 186) and Fuel Pump Off (page 187) are invisible until configuration of
this LBO.
Fuel Pump
6 back to Logical binary outputs alphabetically
Related FW 1.2.1 Related applications AMF, MRS
Comm object 22
Description
This output controls the fuel solenoid valve. The Fuel Solenoid output has two different behaviors depending
on engine type – gas or diesel. This setting is done by Fuel Solenoid (page 164) setpoint in Engine Settings
group.
Fuel Solenoid