InteliLite Global Guide
186
Setpoint group Engine settings Related FW 1.2.1
Range [units] 0 .. 600 [s]
Default value 5 s Alternative config NO
Step s
Comm object 14683 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
When the value of fuel drop per hour is higher than Maximal Fuel Drop (page 185) this delay stars count down.
After count down of this delay alarm Wrn Fuel Thief (page 569) is activated.
Maximal Fuel Drop Delay
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.2.1
Range [units]
0 .. Fuel Pump Off (page 187) [%]
Default value 20 % Alternative config NO
Step 1 %
Comm object 10100 Related applications AMF, MRS
Config level Advanced
Setpoint visibility
Visible only if the logical binary output FUEL PUMP (PAGE 493) is configured and
logical binary input FUEL PUMP ON/OFF (PAGE 454) isn’t configured
Description
Threshold level for switching the binary output FUEL PUMP (PAGE 493) on.
Image 8.13 Fuel Pump On
IMPORTANT: When binary input FUEL PUMP ON/OFF (PAGE 454) is configured then binary
output FUEL PUMP (PAGE 493) is control by this binary input. Setpoints Description (page 186)
and Fuel Pump Off (page 187) are not evaluated!
Note: Value from analog input has higher priority than ECU.
Note: This setpoint is visible only if the logical binary output FUEL PUMP (PAGE 493) is configured.
Fuel Pump On
6 back to List of setpoints