Setpoint group Engine settings Related FW 1.2.1
Range [units] 1 .. 10 [-]
Default value 3 Alternative config NO
Step 1
Comm object 8255 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Maximal number of cranking attempts.
Cranking Attempts
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.2.1
Range [units] 1 .. 255 [s]
Default value 5 s Alternative config NO
Step 1 s
Comm object 8256 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
Maximum time limit of cranking time.
IMPORTANT: There is a protection against broken pinion on starter. In case that there are no
RPM after 5 seconds of starting, cranking is interrupted and cranking fail pause follows.
Maximum Cranking Time
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.2.1
Range [units] 5 .. 60 [s]
Default value 8 s Alternative config NO
Step 1 s
Comm object 8257 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
Pause between Cranking Attempts (page 165). PRESTART (PAGE 506) output is active in this pause until
Cranking Fail Pause elapses.
Cranking Fail Pause
6 back to List of setpoints

Table of Contents

Other manuals for ComAp InteliLite MRS16

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite MRS16 and is the answer not in the manual?

ComAp InteliLite MRS16 Specifications

General IconGeneral
BrandComAp
ModelInteliLite MRS16
CategoryController
LanguageEnglish

Related product manuals