EasyManua.ls Logo

ComAp InteliLite MRS16 - Page 506

ComAp InteliLite MRS16
632 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
InteliLite Global Guide
506
LBO: P
Related FW 1.2.1 Related applications AMF, MRS
Comm object 290
Description
This is an output from the Power switch function. The behavior of the switch depends on the adjustment of
the setpoints Power Switch On (page 190) and Power Switch Off (page 192). When the dummy load function is
used the switching ON of Power switch is block when the engine isn’t running and is allowed 30 s after start
of the engine.
Image 8.179 Power Switch
Note: Setpoints Power Switch On (page 190) and Power Switch Off (page 192) are invisible until
configuration of this LBO.
Power Switch
6 back to Logical binary outputs alphabetically
Related FW 1.2.1 Related applications AMF, MRS
Comm object 36
Description
This output can be used for control of any device, which has to be activated just before start. The output is
closed for time period of Prestart Time (page 166). The output opens 100 ms before the STARTER (PAGE 510)
output closes.
Image 8.180 Engine start
Prestart