InteliLite Global Guide
507
When the Prestart Time (page 166) is longer than Cranking Fail Pause (page 165) then the Prestart Time (page
166) in Cranking Fail Pause (page 165) is long as Cranking Fail Pause (page 165) minus 100ms.
Image 8.181 Prestart in Cranking Fail Pause 1
When the Prestart Time (page 166) is shorter than Cranking Fail Pause (page 165) then the Prestart Time (page
166) in Cranking Fail Pause (page 165) is long as normal Prestart Time (page 166).
Image 8.182 Prestart in Cranking Fail Pause 2