InteliLite Global Guide
508
LBO: R
Related FW 1.2.1 Related applications AMF, MRS
Comm object 58
Description
The output is closed whenever the GCB is closed or can be closed i.e. the stabilization phase is finished, the
gen-set is running and the Minimal Stabilization Time (page 171) timer has elapsed.
and the gen-set voltage and frequency are within limits.
If GCB is open then gen-set voltage and frequency must be in limits.
If GCB is close then gen-set voltage and frequency can be out of limits, but protection delay can’t be count
down. If gen-set voltage and frequency will return into limits until delay is count down then output is still
closed.
Ready To Load
6 back to Logical binary outputs alphabetically
Related FW 1.2.1 Related applications AMF, MRS
Comm object 62
Description
The binary output is closed, when the engine is stopped and it is possible to start it i.e. no red alarm is
activated or SD OVERRIDE (PAGE 461) is active.
The binary output is switch on when the Ready state occurs.
The binary output is switch off when the Prestart or the Not Ready or the Stop state occurs i.e. always
except Ready state.
Ready
6 back to Logical binary outputs alphabetically
Related FW 1.2.1 Related applications AMF, MRS
Comm object 1372
Description
This output is closed if ECU send signal Regeneration Needed.
RegenerationNeeded
6 back to Logical binary outputs alphabetically

Table of Contents

Other manuals for ComAp InteliLite MRS16

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite MRS16 and is the answer not in the manual?

ComAp InteliLite MRS16 Specifications

General IconGeneral
BrandComAp
ModelInteliLite MRS16
CategoryController
LanguageEnglish

Related product manuals