Setpoint group Engine settings Related FW 1.2.1
Range [units]
8,0 V .. Battery > Voltage (page 190) [V]
Default value 18,0 V Alternative config NO
Step 0,1 V
Comm object 8387 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Warning threshold for low battery voltage.
Battery < Voltage
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.2.1
Range [units]
Battery < Voltage (page 190) .. 40,0 [V]
Default value 36,0 V Alternative config NO
Step 0,1 V
Comm object 9587 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Warning threshold for high battery voltage.
Battery > Voltage
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.2.1
Range [units] 0 .. 600 [s]
Default value 5 s Alternative config NO
Step 1 s
Comm object 8383 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Delay for Battery < Voltage (page 190) and Battery > Voltage (page 190) protection.
Battery <> Voltage Delay
6 back to List of setpoints
Subgroup: Power switch
Setpoint group Engine settings Related FW 1.2.1
Range [units] 0 .. 32 000 [kW]
Power Switch On