InteliLite Global Guide
189
Setpoint group Engine settings Related FW 1.2.1
Range [units] 0 ... 9 999 [h] / Disabled
Default value 1 000 h Alternative config NO
Step 1 h
Comm object 10529 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Maintenance timer 2 counts down when engine is running. If reaches zero, an alarm appears. When the
value 10000 is set, than the Maintenance function is disabled and counter does not count. Counter value
disappear from controllers statistics.
Maintenance Timer 2
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.2.1
Range [units] 0 ... 9 999 [h] / Disabled
Default value 1 000 h Alternative config NO
Step 1 h
Comm object 10530 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Maintenance timer 3 counts down when engine is running. If reaches zero, an alarm appears. When the
value 10000 is set, than the Maintenance function is disabled and counter does not count. Counter value
disappear from controllers statistics.
Maintenance Timer 3
6 back to List of setpoints
Subgroup: Battery Protections
Setpoint group Engine settings Related FW 1.2.1
Range [units] 0 .. 15 [min]
Default value 5 min Alternative config NO
Step 1 min
Comm object 11374 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Conditioned with LBI BATTERY CHARGE (PAGE 450)
Description
Delay for LBI BATTERY CHARGE (PAGE 450).
Battery Charge Fail Delay
6 back to List of setpoints