Setpoint group Engine settings Related FW 1.2.1
Range [units] the range is defined by analog sensor curve
Default value
the value is defined by
analog sensor curve
Alternative config YES
Step the step is defined by analog sensor curve
Comm object 12895 Related applications AMF, MRS
Config level Standard
Setpoint visibility Visible only if the logical analog input OIL PRESSURE (PAGE 546) is configured
Description
Warning or history threshold level for OIL PRESSURE (PAGE 546).
Oil Pressure Wrn
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.2.1
Range [units] the range is defined by analog sensor curve
Default value
the value is defined by
analog sensor curve
Alternative config NO
Step the step is defined by analog sensor curve
Comm object 12779 Related applications AMF, MRS
Config level Standard
Setpoint visibility Visible only if the logical analog input OIL PRESSURE (PAGE 546) is configured
Description
Shutdown threshold level for OIL PRESSURE (PAGE 546).
Oil Pressure Sd
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.2.1
Range [units] 0 .. 900 [s]
Default value 3 s Alternative config NO
Step 1 s
Comm object 14341 Related applications AMF, MRS
Config level Standard
Setpoint visibility
Visible only if the logical analog input OIL PRESSURE (PAGE 546) is configured or
logical binary input OIL PRESSURE (PAGE 458) is configured
Description
Delay for OIL PRESSURE (PAGE 546).
Oil Pressure Delay
6 back to List of setpoints