InteliLite Global Guide
176
Setpoint group Engine settings Related FW 1.2.1
Range [units] 0 .. 50 [%]
Default value 20% Alternative config NO
Step
1 % of Nominal RPM (page 160)
Comm object 14107 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
This setpoint rise the upper limit of overspeed protection for the time which is defined in setpoint Overspeed
Overshot Period (page 176). In this time the upper limit of protection is Overspeed Sd (page 175) + Overspeed
Overshoot.
Note: This function is available only for GASengines (Fuel Solenoid (page 164) = GAS). Also Gear Teeth
(page 160) has to be set to FGen->RPM.
Overspeed Overshot
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.2.1
Range [units] 0 .. 255 [s]
Default value 5 s Alternative config NO
Step 1 s
Comm object 14108 Related applications AMF, MRS
Config level Standard
Setpoint visibility
Conditioned by the setpoint Overspeed Overshot (page 176)
Description
Time for which is Overspeed Overshot (page 176) active. The timer starts in the same time when starter
starts.
Note: The setpoint is visible only, if Overspeed Overshot (page 176) is greater than 0.
Overspeed Overshot Period
6 back to List of setpoints