InteliLite Global Guide
264
Subgroup: Timer 1
Setpoint group Scheduler Related FW 1.2.1
Range [units] Disable / No Func / /Auto Run / Mode OFF [-]
Default value Disable Alternative config NO
Step [-]
Comm object 11660 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
It is possible to choose out of 5 following timer functions. Binary output EXERCISE TIMER 1 (PAGE 492) is
always activated when Timer is active regardless of chosen timer function. Timer functions require controller
running in AUTO mode.
Timer 1 has higher priority over Timer 2. So if Timer 1 Function (page 264) is configured for OFF mode and
Timer 2 Function (page 271) is over the same time configured for AUTO mode, controller will work in OFF
mode.
Controller activates timer whenever it is powered up even in period, where timer should be already running.
Disable The Timer 1 is disabled.
No Func There is no any other function, only binary output Timer 1 is activated.
Auto Run When this option is chosen then the Timer output is internally connected to the REMOTE
START/STOP (PAGE 460) binary input.
Mode OFF When this option is chosen then the Timer 1 binary output is internally connected to the
Remote OFF binary input.
Timer 1 Function
6 back to List of setpoints

Table of Contents

Other manuals for ComAp InteliLite MRS16

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite MRS16 and is the answer not in the manual?

ComAp InteliLite MRS16 Specifications

General IconGeneral
BrandComAp
ModelInteliLite MRS16
CategoryController
LanguageEnglish

Related product manuals