EasyManuals Logo
Home>ComAp>Controller>InteliLite MRS16

ComAp InteliLite MRS16 User Manual

ComAp InteliLite MRS16
632 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #577 background imageLoading...
Page #577 background image
InteliLite Global Guide
577
Alarm Type Other
Alarmlist message EM(A) - configuration mistake
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm indicates that there is a problem with configuration of binary input or
output of module in slot.
EM(A) - configuration mistake
6 back to List of alarms level 1
Alarm Type Other
Alarmlist message EM(A) - insufficient
Alarm evaluated All the time
Related applications AMF, MRS
Description
The alarm indicates that there was a request to send an alarm email to email
address which is adjusted in setpoint Email Address 1 (page 326) and email wasn’t
send.
EM(A) - insufficient
6 back to List of alarms level 1
Alarm Type Other
Alarmlist message EM(A) - missing or damaged
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm indicates that there is a problem with communication with module in slot
(in first 5 second there was no communication and module is configured in slot).
EM(A) - missing or damaged
6 back to List of alarms level 1
Alarm Type Other
Alarmlist message EM(B) - a message lost
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm indicates that there is a problem with communication between controller
and module in slot.
EM(B) - a message lost
6 back to List of alarms level 1

Table of Contents

Other manuals for ComAp InteliLite MRS16

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite MRS16 and is the answer not in the manual?

ComAp InteliLite MRS16 Specifications

General IconGeneral
BrandComAp
ModelInteliLite MRS16
CategoryController
LanguageEnglish

Related product manuals