Alarm Type Other
Alarmlist message EM(A) - configuration mistake
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm indicates that there is a problem with configuration of binary input or
output of module in slot.
EM(A) - configuration mistake
6 back to List of alarms level 1
Alarm Type Other
Alarmlist message EM(A) - insufficient
Alarm evaluated All the time
Related applications AMF, MRS
Description
The alarm indicates that there was a request to send an alarm email to email
address which is adjusted in setpoint Email Address 1 (page 326) and email wasnt
send.
EM(A) - insufficient
6 back to List of alarms level 1
Alarm Type Other
Alarmlist message EM(A) - missing or damaged
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm indicates that there is a problem with communication with module in slot
(in first 5 second there was no communication and module is configured in slot).
EM(A) - missing or damaged
6 back to List of alarms level 1
Alarm Type Other
Alarmlist message EM(B) - a message lost
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm indicates that there is a problem with communication between controller
and module in slot.
EM(B) - a message lost
6 back to List of alarms level 1