InteliLite Global Guide
576
Alarm Type Warning
Alarmlist message Wrn Stop Fail
Alarm evaluated While the engine shall be stopped
Related applications AMF, MRS
Description
This alarm occurs if the gen-set shall be stopped, but some symptom indicates that
it is not stopped. The period when the gen-set shall be stopped begins after the
FUEL SOLENOID (PAGE 493) has been switched off and time delay Stop Time (page
174) has elapsed and lasts for the entire time the FUEL SOLENOID (PAGE 493) or
STARTER (PAGE 510) are off.
Image 9.13 Stop Fail
Note: Gen-set cannot be started until this alarm is inactive and reset.
Wrn Stop Fail
6 back to List of alarms level 1
Other type
Alarm Type Alarm indication
Alarmlist message After-Treatment
Alarm evaluated All the time
Related applications AMF, MRS
Description This alarm occurs when appropriate after-treatment lamp is active.
After-Treatment
6 back to List of alarms level 1
Alarm Type Other
Alarmlist message EM(A) - a message lost
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm indicates that there is a problem with communication between controller
and module in slot.
EM(A) - a message lost
6 back to List of alarms level 1