InteliLite Global Guide
575
Related applications AMF, MRS
Description
This alarm indicates that the oil pressure is lower than the pressure set in Oil
Pressure Wrn (page 177) setpoint.
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Wrn Overload
Alarm evaluated All the time
Related applications AMF, MRS
Description
The alarm is issued when the gen-set power is over the limit for time period longer
than the delay. The following setpoints are related to it:
Overload Wrn (page 194) adjusts the overload limit.
Overload BOC Delay (page 194) Overload Del adjusts the delay.
Wrn Overload
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Override All Sd
Alarm evaluated All the time
Related applications AMF, MRS
Description This alarm occurs when binary input SD OVERRIDE (PAGE 461) is activated.
Wrn Override All Sd
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Wrn Rental Timer 1
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm occurs xx hours before Rental Timer 1 (page 278) elapsed. Hours are
adjusted by setpoint Rental Timer 1 Wrn (page 280).
Wrn Rental Timer 1
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Wrn Rental Timer 2
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm occurs xx hours before Rental Timer 2 (page 280) elapsed. Hours are
adjusted by setpoint Rental Timer 2 Wrn (page 282).
Wrn Rental Timer 2
6 back to List of alarms level 1