Alarm Type Warning
Alarmlist message Wrn Maintenance 1
Alarm evaluated All the time
Related applications AMF, MRS
Description
Adjust the setpoint Maintenance Timer 1 (page 188) to the interval of the next
maintenance check. The value of the setpoint will count down while the engine is
running and if reaches zero, this alarm will be issued. It will continue to count down
to negative values and the alarm message will remain in the alarm list (even if the
controller is switched off and on again) until the setpoint is re-adjusted to a positive
value.
Wrn Maintenance 1
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Wrn Maintenance 2
Alarm evaluated All the time
Related applications AMF, MRS
Description
Adjust the setpoint Maintenance Timer 2 (page 189) to the interval of the next
maintenance check. The value of the setpoint will count down while the engine is
running and if reaches zero, this alarm will be issued. It will continue to count down
to negative values and the alarm message will remain in the alarm list (even if the
controller is switched off and on again) until the setpoint is re-adjusted to a positive
value.
Wrn Maintenance 2
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Wrn Maintenance 3
Alarm evaluated All the time
Related applications AMF, MRS
Description
Adjust the setpoint Maintenance Timer 3 (page 189) to the interval of the next
maintenance check. The value of the setpoint will count down while the engine is
running and if reaches zero, this alarm will be issued. It will continue to count down
to negative values and the alarm message will remain in the alarm list (even if the
controller is switched off and on again) until the setpoint is re-adjusted to a positive
value.
Wrn Maintenance 3
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Wrn Oil Pressure
Alarm evaluated All the time
Wrn Oil Pressure

Table of Contents

Other manuals for ComAp InteliLite MRS16

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite MRS16 and is the answer not in the manual?

ComAp InteliLite MRS16 Specifications

General IconGeneral
BrandComAp
ModelInteliLite MRS16
CategoryController
LanguageEnglish

Related product manuals