Subgroup: Stopping Timers
Setpoint group Engine settings Related FW 1.2.1
Range [units] 0 .. 3 600 [s]
Default value 30 s Alternative config NO
Step 1 s
Comm object 8258 Related applications AMF, MRS
Config level Standard
Setpoint visibility Always
Description
Runtime of the unloaded gen-set to cool the engine before stop.
Cooling Time
6 back to List of setpoints
Setpoint group Engine settings Related FW 1.2.1
Range [units] 0 .. 600 [s]
Default value 60 s Alternative config NO
Step 1 s
Comm object 9815 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
Under normal conditions the engine must certainly stop within this period after the FUEL SOLENOID (PAGE
493) has been de-energized and the STOP SOLENOID (PAGE 511) energized. The stop solenoid remains
energized for the entire stop time period.
Image 8.9 Stop Time 1
Stop Time