InteliLite Global Guide
173
Setpoint group Engine settings Related FW 1.2.1
Range [units] 0 .. 60 [s]
Default value 5 s Alternative config NO
Step 1 s
Comm object 9695 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
In case Fuel Solenoid (page 164) is set to GAS, the Sd Ventilation Time adjusts the time of the starter to be
switched on for engine pre-ventilation in the case of a first start attempt after shutdown or controller switch-
on.
Sd Ventilation Time
6 back to List of setpoints
Subgroup: Stopping
Setpoint group Engine settings Related FW 1.2.1
Range [units] Idle / Nominal [-]
Default value Nominal Alternative config NO
Step [-]
Comm object 10046 Related applications AMF, MRS
Config level Advanced
Setpoint visibility Always
Description
Selects the function of the binary output IDLE/NOMINAL (PAGE 503) during engine cooling state.
Idle Cooling is executed at Idle speed and generator protections are switched off.
Nominal Cooling is executed at Nominal speed and generator protections are active.
Note: When ECU is connected the predefined value 900 RPM for Idle speed is requested.
Note: Binary output IDLE/NOMINAL (PAGE 503) must be configured and connected to speed governor.
Engine Idle speed must be adjusted on speed governor.
Cooling Speed
6 back to List of setpoints