InteliPro, SW version 1.0, ©ComAp – May 2011
InteliPro Reference Guide
4-32
AC Reclosing
AR Delay [ s ]
Delay for activating the AC Reclosing binary output after fault reset.
Step: 0,01 s
Range: 0,00 - 600,00 s
Default setting: 10,00 s
Rec Initiate [ Common / Trp 1 / Trp 2 ]
Selection of which output is considered as a trigger for the AC reclosing function. Deactivation of this
output initiates the counter of AR Delay for reconnecting by the AC Reclosing output.
Common: the output Comm Trp is considered the trigger for AC reclosing counter
Trp 1: the output Trp 1 is considered the trigger for AC reclosing counter
Trp 2: the output Trp 2 is considered the trigger for AC reclosing counter
Default setting: Common
MaxParallTime
MaxParallTime [ s ]
Timer of the maximum parallel time protection.
Step: 1 s
Range: 1 - 1800 s
Default setting: 300 s
MaxPT Block BI [ Block 1 / Block 2 / Block 1+2 / None ]
Selection of blocking binary input for maximum parallel time protection.
Default setting: None
MaxPT Trp BO [ Trp 1 / Trp 2 / Trp 1+2 / None ]
Selection of trip binary output for maximum parallel time protection.
Default setting: None
CU Analog In
Setpoints in this group are used for protection on DC analog inputs of the unit.
CU AI1 Wrn, CU AI2 Wrn, CU AI3 Wrn
Level of warning type of protection assigned to analog input 1, 2 or 3 of the unit respectively. The step,
decimals, range and units are given by configuration of the appropriate output.
CU AI1 Trp, CU AI2 Trp, CU AI3 Trp
Level of trip assigned to analog input 1, 2 or 3 of the unit respectively. The step, decimals, range and
units are given by configuration of the appropriate output.
CU AI1 Del, CU AI2 Del, CU AI3 Del [ s ]
Delay of protections assigned to analog input 1, 2 or 3 of the unit respectively. It is the same for
warning alarm and trip.
Step: 1 s
Range: 0 - 600 s
Default setting: 5 s