13.
K-Factor Settings
Meter Settings
This setting corresponds to the type of meter plugged in to the dispenser. Options 1-3 are for an
encoder meter and depend on the channel setting of this meter. Encoder meters are used for
petrol and diesel, while V50 meters (option 4) are used for LPG and AdBlue. Some settings (such
as temperature and density calibration) are only available for V50 and therefore will not appear if
the meter type is not set to V50.
Variant Settings
This setting should be changed depending on the product set the variant to 0 for liquid fuels
such as petrol or diesel. Set the variant to 4 for diesel emissions fluid (AdBlue). Set the variant to
5 for LPG.
Quantity Settings
This setting is what quantity will be shown on the main display when fuel is being dispensed.
This is only valid for V50 meters and is ignored for encoder meters which always display Litres
uncompensated.
Air Settings
Air switches can be turned on or off to trigger this error, depending on this setting.
Minimum Measurable Quantity (MMQ)
Minimum measured quantity (MMQ) is the minimum amount of fuel that can be dispensed and
measured. The MMQ is calculated with the following equation:
 
With the value in litres. For example, if the coefficient was set to 2, and the exponent was set to
1:
 

So the minimum delivery would be 20 litres.
The exponent can only be certain values;
If the coefficient is 1, the exponent can be 0, 1, 2, 3 (valid values are then 1, 10, 100,
1000)
If the coefficient is 2, the exponent can be 0, 1, 2 (valid values are then 2, 20, 200)
If the coefficient is 5, the exponent can be 0, 1, 2 (valid values are then 5, 50, 500)
If either of the values entered are not valid, or the value is left as 00, the MMQ will be
calculated from the maximum flow. The MMQ is the maximum flow x 0.05. For example, if the
maximum flow was 40 (the default):
  