Pumps have two solenoids for product flow. If the solenoids are unavailable, the pump preset
should also be unavailable. The solenoid delay is the time between when the motor starts, and
when the solenoids start at the beginning of a transaction. The value entered is in seconds.
See Using the Dispenser Menus to edit these settings. Use the procedure for both side A and B.
Preset cutoff is used to deliver an accurate amount of fuel. When dispensing fuel, two solenoids
are used for fuel flow. When the dispensed amount of product reaches the preset cutoff, one
solenoid is turned off to slow delivery rate and dispense an accurate volume of product.
The entered value should be in litres ā for example, if 1.50 is entered, and the preset is 10, the
primary solenoid will cut off once 8.5 litres have been dispensed.
See Using the Dispenser Menus to edit these settings. Use the procedure for both side A and B.