38.
Troubleshooting
Solenoid Not Energising
Check Triac fuse.
Check all Solenoid connections.
Check Solenoid.
If output LEDs on the K-Factor board are off, check nozzle switch operation, the nozzle
switches are working if the Diagnostic LED flashes faster when switch is on.
Select a spare Low Current Solid State Relay if the above checks are okay.
Replace C5000 if fault not found.
Solenoid Not De-energising
If output LEDs on the K-Factor board are on, check nozzle switch is releasing, the nozzle
switch is working if the Diagnostic LED flashes faster when switch is on.
Select spare Low Current Solid State Relay.
Replace C5000 if fault not found.
Preset Display Digit Flashing
Check if any preset buttons are stuck in.
Check wiring & condition of display plugs.
Replace if fault not found.
PIN Pad Not Working
Check that the unit is communicating with the controller using the RD/TD LEDs.
Check connectors are fitted correctly and free of dust.
Replace if fault not found.