EasyManua.ls Logo

Cuenod C 75 - Choosing Fuel Oil Nozzles

Cuenod C 75
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
35
0306 / 13 013 497A
Type
Dual
Fuel
Burner
Power
Fuel oil
flow
Danfoss nozzle
(1) US gal/h
45°B or 60°B
Pump
Pressure
Regul.1 bar Regul.2
kW kg/h 1
st
rate 2
nd
rate
w
1
w
2
C 75
350
400
450
500
550
600
650
750
29,50
33,50
37,80
42,00
46,30
50,60
54,80
63,20
4,5
4,5
4,5
4,5
4,5
4,5
4,5
5,5
3,75
4,5
5,0
6,0
6,0
7,5
8,5
10
14
15
17
16,5
18
18
18
13
13
14
18,5
15
18
15,5
17,5
15
C 100
500
550
600
650
700
800
900
1000
43,50
46,30
50,50
55,00
59,00
67,40
75,80
84,80
4,5
5,0
5,0
5,0
5,0
5,0
5,0
5,0
4,5
5,0
6,0
7,5
8,5
10
11
11
20,5
18
17,5
15
17
18
19
22
23,5
19
17,5
16,5
17,5
18
20
24
Highlighted: delivered equipment. 1kg fuel at 10°C = 11,86kW
(1) Similar nozzles:Danfoss 60°S1
st
rate - Delavan 45° A - Steinen 60° SS
Start up
Choosing nozzles
EN

Related product manuals