Table of Contents

Questions and Answers

  • L
    Laura MayerAug 11, 2025
    What to do if there is no flame at the end of safety time in Cuenod Burner?
    • E
      ellisoncharlesAug 11, 2025
      If there's no flame at the end of the safety time for your Cuenod Burner, you should first check the fuel-oil level in the tank and ensure that all valves are open. If equipped, check and reset the pressure. Then, inspect the pump operation, pressure, coupling, filter, and electric valve. Next, examine the ignition circuit, electrodes, and electrode settings, cleaning the electrodes as necessary. If the issue persists, consider replacing the electrodes, ignition cables, transformer, or nozzle.
  • Z
    zmillerAug 19, 2025
    What to do if Cuenod NC12 runs briefly then stops and emits a signal?
    • T
      teresa33Aug 20, 2025
      If your Cuenod Burner starts briefly, stops, and signals that it was in a set pattern of 9, the control unit may have stopped intentionally or there might be a loss of flame. Try resetting the control unit first. If that doesn't work, clean or replace the flame monitor, reset combustion, and if necessary, replace the control unit.
  • T
    theresa56Aug 26, 2025
    Why Cuenod NC12 fails to start after thermostatic shutdown but the control unit gives no fault signal?
    • R
      rmeyersAug 27, 2025
      If your Cuenod Burner fails to start after a thermostatic shutdown and the control unit shows no fault signal, it could be due to a decrease or absence of supply voltage. Check the origin of this voltage issue. Alternatively, the control unit itself might be defective and need replacement.
  • P
    paceanthonySep 2, 2025
    How to fix parasitic flame during preventilation in Cuenod NC12?
    • G
      Gregory FranklinSep 2, 2025
      If you observe a parasitic flame during preventilation or pre-ignition time in your Cuenod Burner, clean or replace the electric valve, or the pump if it has an integral electric valve.